beautypg.com

Ceiling radiation damper (crd), Discharge installation sp-a 50-90 models – Greenheck SP and CSP (477179) User Manual

Page 4

background image

4

Ceiling Exhaust and Inline Fans

Ceiling Radiation Damper (CRD)

If fan is to be used in a fire resistive membrane
ceiling, a ceiling radiation damper must be used.

If the ceiling radiation damper is already mounted to
the fan from the factory, proceed to Install the Fan.

Attachment Tabs

B-Models

To mount the ceiling radiation damper to fan, make sure
grille attachment tabs are facing down. Then place the inlet
part of the fan into the ceiling radiation damper collar, and
use self-tapping sheet metal screws (by others) to screw
through the damper collar and into the fan housing. If the
fan/light combination is being used, make sure ceiling

radiation damper has
an electrical plug in it.
The electrical plug must
be inserted into the fan.
Make sure the electrical
wire will not interfere with
damper operation as
shown in figure below.

Discharge Installation SP-A 50-90 Models

A-50-510, 710, 780 Models

Wires from lighted grille

Wires to ceiling fan

Do not allow
interference
in this area

A-700, 900-1550 Models

SP-A Box Slot

Plastic SP-A
Duct Adapter Tabs

Insert plastic duct tab into SP-A box slots.

Plastic SP-A
Duct Adapter (PN 473388)

Sheet Metal Screw #10x3/8

Phillips Head (PN 415838)

SP-A Box

Sheet Metal Screw #10x3/8

Phillips Head (PN 415838)

SP-A Box

Plastic SP-A

Duct Adapter (PN 473388)

Screw Tabs

Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)

Screw holes

Rotate plastic SP-A duct adapter (PN 473388)
until the screw tabs meets SP-A box.

1

2

Install screws provided to secure discharge.

3

®