Damper trouble shooting

The following is a cause and correction list for common concerns with the dampers.

Damper Maintenance

Greenheck's dampers are designed to be trouble free and hassle free under normal operation. Dampers are
to be installed square and straight so as to prevent binding during operation. The following annual damper
maintenance suggestions will help to insure proper damper operation and increase the life expectancy of the
damper.

foreign Matter

Over the course of time, dirt and grime may collect on damper surfaces. The

damper surfaces should be cleaned to prevent hindrance to airflow.

Moving Parts

Make sure that parts such as linkage, bearings, blades, etc. that are intended

to move freely, can do so. Lubricating these components can prevent possible

rusting and unnecessary friction increase. Use only a moli-spray oil or similar

graphite based oil as regular lubricating oil will attract dirt.

Bearings.

Synthetic, oil impregnated, and ball bearings (without grease fittings)

do not require lubrication. Ball bearings with grease fittings require only minimal

grease.

Closure

Remove foreign materials that may be interfering with blade closure or effective

sealing of the blades with each other or with the frame.

operation

While operating the damper through its full cycle, check to see that the blades

open and close properly. If there is a problem, check for loose linkage, especially

at the actuator. Tighten the linkage where required.

Symptom

Possible Cause

Corrective Action

Damper does not fully

open and/or fully close

Frame is 'racked' causing blades to
bind on jamb seals

Adjust frame such that it is square and
plumb

Actuator linkage loose

Close damper, disconnect power, adjust
and tighten linkage

Defective motor

Replace

Screws in damper linkage

Locate screws and remove

Actuator linkage hitting wall or floor

Damper installed too far into wall. Move
out to designated line on damper label

Contaminants on damper

Clean with a non-oil-based solvent (see
Damper Maintenance)

468333• ICD Rev. 3, October 2012

Copyright 2012 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change

specifications without notice.

Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in

the Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

This manual is related to the following products: