Damper Troubleshooting
(continued)
Problem
Possible Cause
Solution
Excessive leakage
across damper
Damper not closing fully
Readjust actuator or drive linkage to fully close
damper.
Damper not equipped with
blade and jamb seals
Retrofit with blade seals.
Blade edge seals failed
Replace blade edge seals.
Stop angles not contacting
blade edges
Close damper. Loosen fasteners and adjust stop
angles so as to contact blade.
Caulking failed
Recaulk gaps with silicone sealant as required.
Excessive leakage through
damper frame
No axle seals specified
Contact manufacturer for available modifications.
O-ring axle seals worn
Replace o-rings as required.
Double gland packing not tight
Tighten adjustment nuts on double gland stuffing
box.
Double gland packing worn
Replace packing as required.