Damper Troubleshooting

(continued)

Problem

Possible Cause

Solution

Excessive leakage
across damper

Damper not closing fully

Readjust actuator or drive linkage to fully close
damper.

Damper not equipped with
blade and jamb seals

Retrofit with blade seals.

Blade edge seals failed

Replace blade edge seals.

Stop angles not contacting
blade edges

Close damper. Loosen fasteners and adjust stop
angles so as to contact blade.

Caulking failed

Recaulk gaps with silicone sealant as required.

Excessive leakage through
damper frame

No axle seals specified

Contact manufacturer for available modifications.

O-ring axle seals worn

Replace o-rings as required.

Double gland packing not tight

Tighten adjustment nuts on double gland stuffing
box.

Double gland packing worn

Replace packing as required.