Damper Troubleshooting

Problem

Possible Cause

Solution

Damper does not move

No power to actuator

Verify presence of correct power to actuator.

Actuator failed

Power actuator independently of damper.

Actuator attempting to rotate in
wrong direction

Check wiring. Run actuator independent of damper
if necessary.

Linkage/coupling failed

Inspect coupling, keys, and connecting linkage for
failed or broken components. Replace as required.

No modulating signal

Verify presence of modulating signal.
Verify signal is compatible with actuator.
Verify if signal is driving actuator in the correct
direction.

Obstruction in damper linkage
or inside duct

Inspect for projecting mounting bolts, debris inside
damper and remove.

Damper attempts to move
but, does not open fully

Actuator sizing incorrect
(excessive torque required)

Verify that correct operating pressures, velocities,
and temperatures were given to manufacturer for
actuator sizing. Replace actuator if necessary.

Obstruction in damper linkage
or inside duct

Inspect for projecting mounting bolts, debris inside
damper and remove.

Modulating control not going
full span

Verify control signal span from controller.

Actuator travel stops incorrectly
adjusted

Some actuators are equipped with mechanical
stops to limit rotation. Adjust as necessary.

Damper with jamb seals
installed with blades vertical

Consult factory, for modifications if vertical blade
orientation not specified on damper with seals.

High noise level

Very high velocity/flow

Reduce flow through damper.

No seals on dampers

Retrofit with blade seals.

Damper not closing fully

Readjust actuator or drive linkage to fully close
damper.

The following is a cause and correction list for common concerns with the damper:

Closure

Remove foreign materials that may be interfering with blade closure or effective sealing of the

blades with each other or with the frame.

Blade Seals. Inspect annually. Replacement is recommended after 5 years to reduce the

potential of leakage on HBTR series. Damper serial number required when ordering replacement

seal.

Axle Seals. Inspect and adjust as necessary.

Operation

While operating the damper through its full cycle, check to see that the blades open and close

properly. If there is a problem, check for loose linkage, especially at the actuator. Tighten the

linkage where required.

Actuator

Cycle test actuator per manufacturer’s recommendations.