Page 6

background image

6

Setting the Actuator/Controller's BACnet Configuration

The actuator’s BACnet configuration including the
device instance, MAC address, and baud rate can be
accessed through its Ethernet port.

Connecting to the Actuator

1. Using an Ethernet cable, connect the CAT 5

Ethernet port on your computer to the CAT 5 port
on your actuator.

2. Go into your computer’s Control Panel and access

the Local Area Connection

Windows 7 or 8

• Access the Network and Internet settings

then the Network Sharing Center

• Click on Change adapter settings then right

click on the Local Area Connection and
select Properties

Windows XP

• Open Network Connections

• Right click on the Local Area Connection

and select Properties

Access IP Address Settings

1. Select Internet Protocol

Windows 7 or 8

Select Internet Protocol Version 4 (TCP/IPv4)
the click on Properties

Windows XP

Select Internet Protocol (TCP/IP) the select
Properties

2. Change the IP Address to the value shown below.

Then hit the Tab key and the Subnet mask will
populate. Then click OK.

Access the Actuator

1. Open Internet Explorer and enter the following

address: http://192.168.0.10:8080/index.html

2. Enter "amdsetup" as the User Name and "gfcamd"

as the password.

Entering the BACnet Settings

1. Click on BACnet/MP settings.
2. Select MS/TP as Protocol
3. Configure the desired baud rate and MAC address
4. Choose unique Instance ID
5. Enter desired Device Name (optional)
6. Click Submit button