AMD-xx-TD’s Ordered with a Factory Supplied Controller

When you order a factory supplied controller, it comes with a Greenheck exclusive VAFB24-BAC-GTD actuator
which has the controller integrated inside of it. The actuator/controller is configured by the factory at the time
the unit is ordered for either analog or BACnet operation. This selection is made by setting the Setpoint Source
datapoint to Local AI or BACnet. A complete list of the all the BACnet datapoints is listed in Table 1 (page 7).

AMD-xx-TD Series Dampers with an Analog Factory Supplied Controller

Figure 2 shows field wiring for an AMD-xx-TD ordered with a factory supplied controller configured for analog
operation.

Units ordered without a factory supplied controller
are supplied with a standard modulating actuator.
The Vari-Green transmitter and actuator are wired to
a factory supplied terminal block. Figure 1 shows the
field wiring side of the terminal block.

AMD-xx-TD Series Dampers without a Factory Supplied Controller

The 0-10 VDC analog output at terminals 3 and
4 comes from the Vari-Green transmitter and is
proportional to the velocity going through the
AMD-xx-TD. A 10 VDC signal represents the
maximum velocity that was selected at the time the
unit was ordered. The selected maximum velocity
and the area of the AMD-xx-TD are listed on a label
adjacent to the terminal block. An example of how
you can determine the velocity and/or cfm going
through the unit is shown below.

Example 1:

Determine the CFM from a 24 in.

x 24 in. AMD-xx-TD (area of 4 ft

2

) with a selected

maximum velocity of 2,000 fpm and a voltage reading
across terminals 3 and 4 of 3.5 VDC.

1 2 3 4 5 6

9

7 8

S

S

~

24VAC

0-10VDC Output

Proportional to

Flow

Control

Signal to

Actuator

AMD-XX-TD w/o Factory

Supplied Controller

Factory Installed

Terminal Block

On multiple section high dampers, the

actuators on the sections without the

terminal block will need to be field wired

into Terminals 1, 2, & 5

***

***

1 2 3 4 5 6

9

7 8

S

S

~

24VAC

Factory Installed

Terminal Block

0-10 VDC Output

Proportional to

Flow

0-10VDC

Input

Setpoint

AMD-XX-TD w/Analog

Factory Supplied

Controller

Figure 1

Figure 2

Measured Velocity = Max Velocity * (Measured Voltage / 10)

Measured Velocity = 2,000 * (3.5 / 10)

Measured Velocity = 700 fpm

and

Measured CFM = Measured Velocity * Area

Measured CFM = 700 fpm * 4 ft2

Measured CFM = 2,800 cfm