36
Functional princi-
ple
Scope of supply
(1)
1 x Fronius Power Control Card
(2)
1 x 5-pin plug for connection to the
ripple control signal receiver
(3)
2 x Fronius Solar Net terminating
plugs
not shown:
1 x operating instructions
1 x cardboard packaging (only pro-
vided when retrofitting Fronius
Power Control Cards)
If the Fronius Power Control Card is
integrated in the inverter, the other
components are supplied in a plas-
tic bag.
Prerequisites for
operation of the
Fronius Power
Control Card
-
The Fronius Power Control Card contains all the functionality of the Fronius Com
Card. Having a Fronius Power Control Card and a Fronius Com Card installed in the
same inverter at the same time is not permitted, and is not necessary.
1230 W
Wechselrichter 1
Power
Control Card
Rundsteuer-
Empfänger
1230 W
Wechselrichter 2
Com Card
1230 W
Wechselrichter 3
Com Card
EVU
(1)
(2)
(3)
WARNING! Risk of injury and damage from an electric shock or spark-over. A
Fronius Power Control Card and a Fronius Com Card must never be used in a
device at the same time.
CAUTION! There is a risk of damage from the equipotential bonding of different
DATCOM rings. Only one Fronius Power Control Card may be connected directly
to a ripple control signal receiver.