Connection with
V-type terminal
lug
(1)
Tightening torque 25 Nm
(2)
Tightening torque 6 Nm
Connection with
cable lug
(1)
Tightening torque 28 Nm
(2)
Tightening torque 6 Nm
Connecting the
Fronius String
Control 250/30
DCD DF to the in-
verter
Connect the DC 'OUT' cables to the inverter as described in the inverter operating in-
structions
1
2
1
(1)
(2)
2
NOTE! Note the following points when connecting:
-
Is solar module grounding required or is it already grounded?
If so, note the special features of the respective solar module grounding
-
If the solar module is already grounded, Fronius recommends that you al-
ways use string fuses in the ungrounded branch.
-
Connect the DC 'OUT' cable to the inverter, ensuring that the polarity is cor-
rect