Fronius IG 300 User Manual
Page 69

61
LED is steady orange, po-
wer module then attempts a
restart
425
Communication with
the power module is not
possible
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
Earth current at the solar
modules
434
Earthing fault detected
Check cabling on the DC
side and fuse on the
FRONIUS IG
Fixing voltage is lower than
actual MPP voltage
412
Fixing voltage mode
has been selected in-
stead of MPP voltage
mode, and the fixing
voltage has been set
at too low a value.
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
Because the mains conditi-
ons have changed signifi-
cantly, the power module is
disconnected briefly from
the mains.
413
Control problems
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
Memory component erased
414
EEPROM defective
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
LED is steady orange, po-
wer module then attempts a
restart
416
Communication with
IG-Ctrl not possible
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
Power module locked out,
critical error indicated by red
LED
417
Two power modules
have the same PCB
number
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
Power module locked out,
critical error indicated by red
LED
419
Two or more power
modules with identical
software serial number
detected
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
Power module locked out,
critical error indicated by red
LED
421
PCB number has been
set incorrectly
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
Class 4
(continued)
FRONIUS IG is not con-
nected to the mains
439
Transformer not con-
nected
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
FRONIUS IG is not con-
nected to the mains
440
Jumper short circuit
If a service code appears
frequently: Notify FRO-
NIUS-trained service
engineer
Code
Designation
Manifestation
Remedy