Maintenance – Flowserve UNA 14 User Manual
Page 17
17
Clean trap
1. Remove cover I from body B, fig. 3
2. Lever control unit L M N off its support using a screwdriver, fig. 4
3. Remove old cover gasket O.
4. Clean body and internals.
5. Clean seating surfaces of body and cover. Insert new gasket O.
6. Position control unit on support and fix it by sharp blows, fig. 5
7. Apply heat-resistant lubricant to seating surfaces of cover and threads of fixing screws (use for
instance WINIX
®
2150).
8. Insert a new gasket and put cover onto trap body. Tighten body screws P in diagonally opposite
pairs to a torque of 35 Nm. Retighten screws after the commissioning procedure.
Clean/replace control unit
1. Remove cover I from body B, fig. 3
2. Lever control unit L M N off its support using a screwdriver, fig.4
3. Remove old cover gasket O.
4. Clean seating surfaces of body and cover. Insert new gasket O.
5. Position new or cleaned control unit L M N on support and fix it by sharp blows, fig. 5
6. Apply heat-resistant lubricant to seating surfaces of cover and threads of fixing screws (use for
instance WINIX
®
2150).
7. Insert a new gasket and put cover onto trap body. Tighten body screws in diagonally opposite pairs
to a torque of 35 Nm. Retighten screws after the commissioning procedure.
WINIX
®
2150 is a registered trademark of WINIX GmbH, Norderstedt
GESTRA steam traps UNA 14, UNA 16, UNA 16 A do not require any special maintenance. However,
if used in new installations which have not been rinsed it may be necessary to check and clean the
trap.
The GESTRA air trap UNA 14 P does not require any special maintenance. If, however, the trap is
used with very oily condensate we recommend to clean the trap at regular intervals or to install an
oil separator upstream of the trap.
Maintenance