Installation – Flowserve UNA 14 User Manual
Page 13
13
Name plate / Marking
Ratings and design as specified in EN 19 and EN ISO 26652 on name plate which is firmly attached
to the trap body/cover.
■
Type designation
UNA 1 ...h:
horizontal design
UNA 1 ...v:
vertical design
■
SIMPLEX or DUPLEX:
type of control unit (see “Description”)
additional “P”:
with Perbunan
®
valve ball (max. 40 °C)
additional “R”:
provided with internal venting pipe
■
O...(orifice):
installed orifice
■
Stamp on name plate, e. g. indicates term and year of production
(Example: 4
th
quarter 2003)
Corrosion resistance
If the unit is used for the intended purpose, its safety is not impaired by corrosion.
Sizing
The trap body must not be subjected to sharp increases in pressure.
The dimensional allowances for corrosion reflect the latest state of technology.
UNA 14, UNA 16, UNA 16 A, UNA 14 P
Installation
Float-operated steam traps can – depending on the design of the trap body – be installed in
horizontal or vertical lines with downward flow. Conversion to obtain a different flow direction
is possible:
Flanged design
1. Observe position of installation. The name plate E must always be on top.
2. Observe the direction of flow. The arrow indicating the flow direction A is on the trap body.
Change direction of flow of UNA 14, UNA 16, UNA 16 A or UNA 14 P if necessary.
3. Consider space required for opening trap. When the trap is installed a minimum space of at least
120 mm is required for removing the cover I!
4. Remove plastic plugs. They are only used as transit protection.
5. Clean seating surfaces of both flange faces.
6. Install trap.
Perbunan
®
is a registered trademark of Bayer AG, Leverkusen
Design
Control unit
TMA
PN / Class
DN
Name plate
must be on top
Orifice
4
03
Design
Control unit
TMA
PN / Class
Name plate
must be on top
DN
Orifice