Table node id, Decommissioning, Table node id decommissioning – Flowserve NRS1-40.1 User Manual
Page 32: Annex

32
– continued –
Tab le Node ID
In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each node has its own ad-
dress (node ID). This address can be set via a 10-pole code switch
(Factory setting)
(Example)
Decommissioning
First unplug the terminal strips
,
. For this purpose turn the right and left fixing screws
in direction
of the arrow until the terminal strip can be removed.
Undo the fixing slide in order to snap out the controller and take it off the supporting rail.
Node ID
1
Node ID
71
S1
ON
1
S1
ON
1
S2
OFF
2
S2
OFF
2
S3
OFF
4
S3
ON
4
S4
OFF
8
S4
ON
8
S5
OFF
16
S5
OFF
16
S6
OFF
32
S6
OFF
32
S7
OFF
64
S7
ON
64
S 8
S9
S 10
Baud rate
Cable length
OFF
ON
OFF
250 kBit /s
125 m
Factory setting
ON
ON
OFF
125 kBit /s
250 m
OFF
OFF
ON
100 kBit /s
335 m
ON
OFF
ON
50 kBit /s
500 m
OFF
ON
ON
20 kBit /s
1000 m
ON
ON
ON
10 kBit /s
1000 m
D
ON
1 2 3
5
4
6 7 8 9 10
D
Toggle switch, white
ON
1 2 3
5
4
6 7 8 910
D
Toggle switch, white
A
B
C