Flowserve MX Dashboard Limitorque User Manual
Page 20

20
FCD LMENIM2338-01
Viewing trace Data
Selecting	View	Trace	Data	will	result	in	the	following	display	
presuming valid collection of data. The FDA Trace supports 
data comparison to an existing saved file.
FDA Trace
Speed Trace
FDA and sPeeD Analysis explanation
The values for the X-axis are in RPM. The values for the Y-axis 
are the relative magnitude of the power that the various rotating 
components of the actuator are developing mechanically over 
the speed ranges. If the magnitude at any given RPM changes 
from the stored baseline FDA, then compare the x-axis RPM 
for the suspect power magnitude against the expected working 
RPM for the components in the actuator. Any component that 
is expected to operate at the suspect RPM could be at risk 
of excessive wear, and the actuator should be included in a 
targeted preventive maintenance program. The suspect parts 
could be ordered in advance of the preventive maintenance to 
ensure that the downtime will be minimized.
Note: At the current time, the power magnitudes are relative 
values.
Operation Log lists parameters associated with the MX/QX 
operation since the last reset. This function is a real-time log.