Acknowledge handler class code: 43 (0x2b), Worcester controls – Flowserve Worcester Controls Supplement 1 ACCESS I User Manual
Page 5
![background image](https://www.manualsdir.com/files/784915/content/doc005.png)
WCAIM2012
Supplement 1 – ACCESS I and M DeviceNet Specification
5
Common Services
Implemented For:
Service Code
Class
Instance
Service Name
14 (0x0E)
Yes
Yes
Get_Attribute_Single
(1) Max Object Instance = 5
(2) Input Value determines overall condition of inputs. The LED
indicators will reflect state of inputs.
State
x
Interpretation
OFF
0
Input is OFF. LED is OFF
ON
1
Input is ON. LED is ON
Discrete Output Point (DOP) Object
Class Code: 09 (0x09)
The Discrete Output Point (DOP) Object models discrete inputs in a
product. You can use this object in applications as simple as a toggle
switch or as complex as a discrete I/O control module. There is a
separate instance for each discrete output available on the device.
DOP Object Class Attributes
Attribute
Access
Name
Type
Value
1
Get
Revision
UINT
1
2
Get
Max Object Instance
UINT
7
6
Get
Max Class Identifier
UINT
7
7
Get
Max Instance Attribute
UINT
8
DOP Object, Instance 1…2 Attributes
Attribute
Access
Name
Type
Value
3
Get/Set
Value
BOOL
(1)
4
Get
Status
BOOL
(1)
5
Get/Set
Fault State
BOOL
(2)
6
Get/Set
Fault Value
BOOL
(2)
7
Get/Set
Idle State
BOOL
(3)
8
Get/Set
Idle State
BOOL
(3)
Common Services
Implemented For:
Service Code
Class
Instance
Service Name
14 (0x0E)
Yes
Yes
Get_Attribute_Single
16 (0x10)
No
Yes
Set_Attribute_Single
(1) Output Value and Status determine overall condition of outputs.
State
x
Interpretation
OFF
0
Output is OFF
ON
1
Output is ON
State
x
Interpretation
OK
0
Output is OK
FAULT
1
Output is at FAULT
(2) The Fault Value and Fault State determine the unit’s reaction to an
output fault condition.
Under normal operation the status information has the same state
as Output value. If a fault condition is detected the status is the
complement of the Output value.
State
x
Interpretation
0
0
Turn output OFF and OK
1
1
Turn output ON and OK
0
1
Turn output OFF and faulted
1
0
Turn output ON and faulted
(3) The Idle Value and Idle State determine the unit’s reaction to an
output idle condition.
State
x
Interpretation
0
0
Turn output OFF if idle
0
1
Turn output ON if idle
1
x
Leave output unchanged if idle
Acknowledge Handler
Class Code: 43 (0x2b)
The Acknowledge Handler is used to manage the reception of
message acknowledgements.
Acknowledge Object, Class Attributes
Attribute
Access
Name
Type
Value
1
Get
Revision
UINT
1
Acknowledge Object, Instance 1 Attribute
Attribute
Access
Name
Type
Value
1
Get/Set
Acknowledge Timer
UINT
(1)
2
Get/Set
Retry Counter
USINT
(2)
3
Get
COS Producing
UINT
4
Connection Instance
Common Services
Implemented For:
Service Code
Class
Instance
Service Name
14 (0x0E)
Yes
Yes
Get_Attribute_Single
16 (0x10)
No
Yes
Set_Attribute_Single
(1) The Acknowledge Timer sets the interval after which new data can
be produced.
(2) Retry counter sets the number of times the COS/Cyclic message is
sent.
Flow Control