Supplement 1 – ACCESS I and M DeviceNet Specification
WCAIM2012
Implemented For:
Service Code
Class
Instance
Service Name
05 (0x05)
No
Yes
Reset
14 (0x0E)
Yes
Yes
Get_Attribute_Single
(1) Vendor ID is 469
(2) Device Status
bit 0
owned
0=not owned
1=owned (allocated)
bit 1
reserved
0
bit 2
configured
0
bit 3
reserved
0
bit 4-7
vendor specific
0
bit 8
minor cfg. fault
0=no fault
1=minor fault
bit 9
minor device fault
0=no fault
1=minor device fault
bit 10
major cfg. fault
0=no fault
1=major cfg. fault
bit 11
major device fault
0=no fault
1=major device fault
bit 12-15
reserved
0
(3) Unique Serial Number
(4) Present state of the device
value 0
Nonexistent
value 1
Device Self-Testing
value 2
Standby
value 3
Operational
value 4
Major Recoverable Fault
value 5
Major Unrecoverable Fault
Router Object
Class Code: 02 (0x02)
The Message Router Object provides a messaging connection point
through which a Client may address a service to any object class or
instance residing in the physical device.
Router Object Class Attributes
Attribute
Access
Name
Type
Value
1
Get
Revision
UINT
1
6
Get
Max Class Identifier
UINT
7
7
Get
Max Instance Attribute
UINT
2
Router Object, Instance 1 Attributes
Attribute
Access
Name
Type
Value
2
Get
Number of Connections UINT
4
Common Services
Implemented For:
Service Code
Class
Instance
Service Name
14 (0x0E)
Yes
Yes
Get_Attribute_Single
16 (0x10)
No
Yes
Set_Attribute_Single
DeviceNet Object
Class Code: 03 (0x03)
DeviceNet Object Class Attributes
Attribute
Access
Name
Type
Value
1
Get
Revision
UINT
1
Router Object, Instance 1 Attributes
Attribute Access
Name
Type
Value
1
Get/Set
MACID
USINT
(1)
2
Get/Set
Baud Rate
USINT
(2)
3
Get/Set
Bus Off Interrupt
BOOL
(3)
4
Get/Set
Bus Off Counter
USINT
(4)
5
Get/Spc
Allocation Information
STRUCT of (5)
Choice Byte
BYTE
Master Node Address
USINT
6
Get
MAC ID
BOOL
0 = No Change
Switch changed
1= Changed since
last Reset or
Power-up.
7
Get
MAC ID
BOOL
0 = No Change
Switch Value
1= Changed since
last Reset or
Power-up.
8
Get
MAC ID
USINT
Range 0 - 63
Switch Value
9
Get
Baud Rate
USINT
Range 0 - 2
Switch Value
Common Services
Implemented For:
Service Code
Class
Instance
Service Name
14 (0x0E)
Yes
Yes
Get_Attribute_Single
16 (0x10)
No
Yes
Set_Attribute_Single
75 (0x4B)
No
Yes
Allocate Master/Slave
76 (0x4C)
No
Yes
Release Master/Slave
(1) Settable only if switch 7/8 are both in the ON position. Value
returned will be switch 1..6 or last value set. (Attributes 6-8 are
not implemented in this configuration.)
(2) Settable by switch 7/8 or through DeviceNet if switch 7 and 8 are
both on.
Switch/Value
Speed
0
125 kbits
1
250 kbits
2
500 kbits
3
undefined
(3) Bus Off Interrupt (BOI) determines action if Bus Off state
encountered. Following values are supported:
BOI
Action
0
Hold chip in OFF state (default)
1
If possible reset CAN chip
Flow Control
Worcester Controls