Limitorque LY Series: LY 1001, LY 2001 and LY 3001 FCD LMENIM1501-00 – 11/11

26

Figure 5.13 – Potentiometer Calibration Components

4. If the reading is not correct, proceed to Step 5. If the reading is correct, proceed to Step 6.

5. a. Loosen the small Set Screw that retains the Spur Gear to the Potentiometer Shaft.

b. Using a small flat-tipped screwdriver in the slotted Potentiometer Shaft, rotate the Shaft until
the correct reading is obtained as described in Step 3.

c. Retighten the Set Screw.

6. Disconnect the ohmmeter and reconnect the Potentiometer wiring to the original connection.

Limitorque

PERCENT OPEN

0

50 100

Potentiometer Shaft

Spur Gear

Setscrew

End Connection

Center Connection

Ohmmeter to Pot Leads

Potentiometer

Drive Gear