MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11
68
Transducer Block Parameters
Description
Subparameter R7_FUNCTION
Function assigned to the relay.
Subparameter
R7_CONTACT_TYPE
User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.
Subparameter R7_POSITION
The relay gets energized when the actuator moves the valve to
this user configurable position.
Subparameter R8_FUNCTION
Function assigned to the relay.
Subparameter
R8_CONTACT_TYPE
User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.
Subparameter R8_POSITION
The relay gets energized when the actuator moves the valve to
this user configurable position.
ACT_OPT_FEATURES
Software features that are enabled.
Bit 00 to Bit 05 Not used
Bit 06 Arctic
Bit 07 Two speed timer
TST_CLOSE
Record provides support for configuration of close two speed
timer.
Subparameter STATUS
On/off status of close two speed timer. Value 1=On and 2=Off.
Subparameter START_POSITION
Close two speed timer start position. Range 1 to 1000.
Subparameter STOP_POSITION
Close two speed timer stop position. Range 0 to 999.
Subparameter ON_TIME
Close two speed timer on time. Range: 1 to 20sec. Increment:
0.5sec.
Subparameter OFF_TIME
Close two speed timer off time. Range: 1 to 200sec. Increment:
1sec.
TST_OPEN
Record provides support for configuration of open two speed
timer.
Subparameter STATUS
On/off status of open two speed timer. Value 1=On and 2=Off.
Subparameter START_POSITION
Open two speed timer start position. Range 0 to 999.
Subparameter STOP_POSITION
Open two speed timer stop position. Range 1 to 1000.
Subparameter ON_TIME
Open two speed timer on time. Range: 1 to 20sec. Increment:
0.5sec.
Subparameter OFF_TIME
Open two speed timer off time. 1 to 200sec. Increment: 1sec.
DIAG_DATA
Cumulative device diagnostic data.
ACT_SERVICE_TIME
The cumulative service time of the actuator.
COUNTERS
Record provides support for monitoring all the operation log
counters.
Subparameter
MOTOR_RUN_TIME
Total motor operation time in seconds.