Flowserve MX FOUNDATION Fieldbus Field Unit User Manual
Page 59

59
MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11
flowserve.com
Transducer Block Parameters
Description
Subparameter 0
uint16_var
Unused
Subparameter 1
uint16_var
TP_START_POSITION – The position of the actuator when this
sampling period began (0 to 100% OPEN)
Subparameter 2
uint16_var
TP_STOP_POSITION – The position of the actuator when this
sampling period ended (0 to 100% OPEN)
Subparameter 3
uint16_var
TP_SAMPLE – The number of times that the torque value was sampled
for this TP sample. This value is also relative indicator of cycle
time and may be trended to identify when actuator performance is
changing. Cycle time is approximately equal to “TP Samples” times 50
milliseconds.
Subparameter 4
uint16_var
TP_MID_T_HIGH – The highest relative torque observed in midtravel
during this TP sample.
Subparameter 5
uint16_var
TP_MID_T_POS – The position of the actuator (0 to 100% OPEN) when
the highest mid-travel torque was observed.
Subparameter 6
uint16_var
TP_MID_T_AV_VAL – The average relative torque observed during this
TP sample.
Subparameter 7
uint16_var
TP_STOP_VAL – The relative torque observed at the moment when the
valve motion ended, completing this TP sample.
Subparameter 8
uint16_var
TP_BEFORE_MID_T_HIGH – The highest relative torque observed
while the actuator is in motion but before the limit switch was cleared
indicating that the actuator is in mid-travel. For example, if moving from
the CLOSED position, in the OPEN direction, this value represents the
highest relative torque value observed before the CLOSED limit switch
became inactive.
Subparameter 9
uint16_var
TP_AFTER_MID_T_HIGH – The highest relative torque observed
while the actuator is in motion after the limit switch became active
indicating that the actuator is no longer in mid-travel. For example, if
torque seated and moving from mid-travel, in the CLOSE direction, this
value represents the highest relative torque value observed after the
closed limit switch became active but before the torque switch stopped
movement.
SOFTWARE_VERSION
Device software version
FACTORY_DIAGNOSTIC
Internal use only
DOWNLOAD_PARAMETER
Internal use only
TARGET_ERROR
Internal use only
DTM_ARGUMENT
DTM specific parameter used in conjunction with DTM_COMMAND_ID
parameter for device manufacturer custom operations.
DTM_COMMAND_ID
DTM specific parameter used in conjunction with DTM_ARGUMENT
parameter for device manufacturer custom operations.
BULK_DATA
DTM specific parameter used for device manufacturer custom opera-
tions of uploading bulk data to DTM.
HARDWARE_FAULTS
The bit enumerated parameter provides hardware fault information
such as alarms and warnings. Bit value 1 indicates presence of alarm/
warning condition in the actuator.
Bit 00 SPI bus communication
Bit 01 to Bit 09 Not used
Bit 10 Valve jammed