Transducer Block Parameters
Description
Subparameter R3_FUNCTION
Function assigned to the relay.
Subparameter
R3_CONTACT_TYPE
User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.
Subparameter R3_POSITION
The relay gets energized when the actuator moves the valve to
this user configurable position.
Subparameter R4_FUNCTION
Function assigned to the relay.
Subparameter
R4_CONTACT_TYPE
User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.
Subparameter R4_POSITION
The relay gets energized when the actuator moves the valve to
this user configurable position.
Subparameter RM_SETTINGS
The monitor relay indicates the actuator is available for remote
operation.
Bit 00 to Bit 02 Not used
Bit 03 ESD signal
Bit 04 Inhibit signal
Bit 05 Over torque
Bit 06 Local stop/off
Bit 07 Local selected
OPT_DIGITAL_OUTPUT_RELAYS
Configuration for R5, R6, R7 and R8 relays on optional digital
output relay board.
Subparameter ENABLED
Digital output relays enabled status. Value 0=Disabled and
1=Enabled.
Subparameter STATUS
Contact operation status.
Bit 00 to Bit 03 Not used
Bit 04 R8 contacts status
Bit 05 R7 contacts status
Bit 06 R6 contacts status
Bit 07 R5 contacts status
Subparameter R5_FUNCTION
Function assigned to the relay.
Subparameter
R5_CONTACT_TYPE
User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.
Subparameter R5_POSITION
The relay gets energized when the actuator moves the valve to
this user configurable position.
Subparameter R6_FUNCTION
Function assigned to the relay.
Subparameter
R6_CONTACT_TYPE
User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.
Subparameter R6_POSITION
The relay gets energized when the actuator moves the valve to
this user configurable position.