2 safety critical user wiring – Flowserve MX Electronic Actuator SIL Safety IOM User Manual
Page 13

13
Limitorque MX Electronic Actuator FCD LMENIM2350-01 – 9/13
flowserve.com
FLOWSERVE PROPRIETARY INFORMATION
Use or disclosure of this information is subject to the restrictions on the title page of this document
4.2.2 Safety Critical User Wiring
The LimiGard concept can be extended to user wiring as shown in Safety Block Diagram - Enhanced User Wiring
(Figure 4.2 below) and configuring the actuator in accordance with subsection 10.5, Custom Input Mode - Momentary
ESD/PSESD (Optional).
NOTE: With enhanced PST/ESD configuration, a momentary ESD demand signal will be honored by the actuator, even if
user wiring is subsequently destroyed during the emergency event.
Figure 4.2 - Safety Block Diagram - Enhanced User Wiring
Case A‐B‐C‐D Meaning Action
Monitor Relay
De‐energises?
1
0001
Invalid STOP
Yes
2
0010
CLOSE
No
3
0011
Invalid STOP
Yes
4
0100
CLOSE
No
5
0101
Invalid STOP
Yes
6
0110
Invalid STOP
Yes
7
0111
STOP
No
8
1000
Invalid STOP
Yes
9
1001
OPEN
No
10
1010
Invalid STOP
Yes
11
1011
Invalid STOP
Yes
12
1100
OPEN
No
13
1101
Invalid STOP
Yes
14
1110
Invalid STOP
Yes
15
1111
Invalid STOP
Yes
Case A‐B‐C‐D Meaning Action
Monitor Relay
De‐energises?
1
0001
Invalid STOP
Yes
2
0010
LOCAL
Yes
3
0011
Invalid STOP
Yes
4
0100
LOCAL
Yes
5
0101
Invalid STOP
Yes
6
0110
Invalid STOP
Yes
7
0111
STOP
Yes
8
1000
Invalid STOP
Yes
9
1001 REMOTE
No
10
1010
Invalid STOP
Yes
11
1011
Invalid STOP
Yes
12
1100 REMOTE
No
13
1101
Invalid STOP
Yes
14
1110
Invalid STOP
Yes
15
1111
Invalid STOP
Yes