Technical data, Fig. 1 – Flowserve PA46 User Manual
Page 10
0
Fig. 1
Technical Data
continued
Capacity chart PA 46, PA 47, MPA 46, MPA 47
Calculation of the amount of boiler water to be discharged
according to the following formula:
A = Q · S
K – S
Conductivity of
feedwater:
S [µS/cm]
Admissible conductivity
of boiler water:
K [µS/cm]
Boiler capacity:
Q [kg/h]
Amount of boiler water
to be discharged:
A [kg/h]
Example
Conductivity of
feedwater:
S = 0 µS/cm
Admissible conductivity
of boiler water:
K = 4000 µS/cm
Boiler capacity:
Q = 000 kg/h
Amount of boiler water
to be discharged:
A
≈ 0 kg/h
How to read chart fig. 1
Boiler pressure:
5 bar
Nominal size of intermittent valve for removing boiler
sludge
DN 3
Capacity:
.5 kg/s