Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07

L

13

on of the Logix 3400IQ digital positioner is done almost exclusively in the transducer block

w.

the

be viewed or modified. Check the Periodic Update box to

rizes basic configuration of a Logix 3400IQ digital positioner on a 25 square-inch

Table 1:

Q Digital P

ters

ogix 3400IQ Digital Positioner Configuration

onfigurati

C
(FVPTB).

pen the transducer block (FVPTB) window by double-clicking its tag in the main NI Configurator windo

O
The FVPTB MODE_BLK: TARGET parameter must be set to OOS in order to do any configuration.

Due to the large number of parameters in the FVPTB configuration is easiest under the Custom tab. Use

ustom Config button to select parameters to

C
ensure that the data being viewed is current.

he following table summa

T
actuator and linear valve.

Logix 3400I

ositioner Parame

Parameter

Default

Value

Function

MODE_BLK:TARGET

OOS

Determines the mode of the function block

FINAL_VALUE

No default

positioner before characterization,

Command going to
soft stops or MPC.

FINAL_VALUE_CUTOFF_HI

110%

This will saturate the actuator in an open position if
FINAL_VALUE becomes greater than the cutoff value.

FINAL_VALUE_CUTOFF_LO 1%

r. The new

This will saturate the actuator in a close position if
FINAL_VALUE becomes less than the cutoff value.
This is the same has the Minimum Position Cutoff
feature of the Logix 1200 digital positione
terminology matches FF terminology

FINAL_POSITION_VALUE

Dynamic

Actual stem position in percent of stroke

FINAL_VALUE_RANGE

to -

10%

e

d to display the final value.

110%

The high and low range limit values, the engineering
units code and the number of digits to the right of th
decimal point to be use

DAC_PERCENT

Dynamic

DAC output in percent

CONTROL_FLAGS

dip switch

Used to tell positioner type of actuator and
characterization to use. Note: Must match
settings.

GAIN_UPPER

2

Maximum proportional gain used.

GAIN_LOWER

1

Minimum proportional gain used.

GAIN_MULT

0.05

change between GAIN_UPPER and

.

Adjust the rate of
GAIN_LOWER

IGAIN

10

Integral gain.

IL_OFFSET

30-70%

null position

DAC value to hold spool in a

SOFTSTOP_HIGH

110%

Software upper stroke limit

SOFTSTOP_LOW

-10%

Software lower stroke limit

PRESS_UNITS

expressed in.

Psi

Units pressure sensors reading are

TEMP_UNITS

Deg F

Units temperature is expressed in.


To set the FVPTB in OOS mode, double-click on MODE_BLK: TARGET, in the pop up box check the OOS
box. Click the Write button. With the block mode is set to OOS (MODE_BLK: ACTUAL = OOS), editing

arameters is now permitted. To change or edit a parameter, double-click on the va

the

lue, and make the

hanges in the Edit box. Remember to click the Write button to apply the change.

p