P5 ep5 – Flowserve PMV P4 User Manual
Page 26

26
P5
EP5
Input Signal
20-100 kPa/3-15 Psi (6-30 optional)
4-20 mA
Linearity
≤ 0,5%*
≤ 0,5%*
Hysteresis
≤ 0,75%*
≤ 0,5%*
Repeatability
≤ 0,5%*
≤ 0,5%*
Gain
(pressure 600 kPa/87 Psi)
1 000 (kPa/kPa)
Min 66%/% ISA S75.13
Air consumption at Supply pressure:
0,2 MPa/29 Psi
5,4 nl/min 0.19 SCFM
6,1 nl/min 0.22 SCFM
0,4 MPa/58 Psi
12,3 nl/min 0.43 SCFM
13,6 nl/min 0.48 SCFM
0,6 MPa/87 Psi
20 nl/min 0.71 SCFM
22 nl/min 0.78 SCFM
0,8 MPa/116 Psi
27,8 nl/min 0.98 SCFM
30,5 nl/min 1.08 SCFM
1 MPa/145 Psi
35,7 nl/min 1.26 SCFM
39 nl/min 1.38 SCFM
Air delivery at Supply Pressure:
0,2 MPa/29 Psi
200 nl/min 6.9 SCFM
0,4 MPa/58 Psi
370 nl/min 12.8 SCFM
0,6 MPa/87 Psi
540 nl/min 18.8 SCFM
0,8 MPa/116 Psi
710 nl/min 24.7 SCFM
1 MPa/145 Psi
880 nl/min 30.6 SCFM
Supply Pressure Max 1 MPa/150 Psi
0,15-1 MPa/21,8-150 Psi
Temperature range -20
°C to +85°C (-4°F to 185°F)
Connector threads
1/4" NPT or G
Gauge threads
1/8" NPT or G
Weight std.
1,1 kg/2.4 lbs
1,5 kg/3.4 lbs
Weight with gauges 1,3 kg/2.9 lbs
1,8 kg/3.9 lbs
Ingress protection
IP 66/NEMA 4
* Per cent of full scale.
(The information in this manual is subject to change without notice.)