3.5 Pressure relief valve reset procedure

The pressure relief valve on the right end of the mani-
fold is factory set at 450 psig (3103 kPa) and should
not require adjustment.

If however, the relief valve setting

has become suspect or the seal requires a lower setting,

follow these steps to reset the pressure relief valve. Do not

exceed 450 psig (3103 kPa).

3.5.1 To prevent accidental over pressurization of

the seal, connect the seal supply port directly

to the seal return port. This will protect the

seal from high pressures during valve adjust -

ment.

3.5.2 Completely close the pressure control

valve on the left end of the manifold.

3.5.3 Completely open the pressure relief valve on

the right end of the manifold.

3.5.4 Start the circulator and allow to run long

enough to remove any air from the system. All

fluid flow should be through the pressure relief

valve and into the reservoir.

3.5.5 Carefully close the pressure relief valve on the

right end of the manifold until the desired pres-

sure is maintained in the system.

3.5.6 Shut down the circulator. The pressure relief

valve is now set at and will not need further

adjustment. Higher adjustment of the pressure

relief valve may cause damage to the pump.

3.5.7 Once the pressure relief valve is set, reset the

pressure control valve setting. Refer to the

previous section of this document.

4

Maintenance

Caution:

Do not attempt to work on this system unless

you have on safety glasses with side shields

and you have completely read and understand

this service manual.

4.1 Electrical/power input

Shut down all electrical power to the circulator prior to

attempting maintenance.

4.2 Service of suction strainers

To service the suction strainer, the circulator pump must

be shut off. Make sure the circulator motor cannot be auto

started. Remove top plate of reservoir. Strainers should be

checked and cleaned every 12 months.

4.3 Customer electrical

It is the customer’s responsibility to provide a control panel

to properly operate the circulator.

4.4 Pressure filter

4.4.1 Caution: Do not attempt to open any lines,

loosen fittings or remove filter canister unless

all pressure gauges read zero pressure.

Be sure that instrument isolation valves are

open to gauges. Always wear safety goggles

with side shields when performing mainte-

nance or making adjustments to the system.

4.4.2 After 8 hours of initial start-up or sooner

per clogging indicator, the filter element

should be changed.

4.4.3 Change element every time the clogging indi-

cator on the filter is in the red service filter

position.

4.5 Questions

Do not hesitate to contact your Flowserve representative

with any questions you have concerning the installation,

operation or maintenance of the circulator.