Forward Fuel Flow Lines

Careful planing, good plumbing practice, and a neat, orderly installation are required to successfully keep the fuel systems
inlet vacuum under 10” Hg, (5 PSI). To achieve this you must:

• Size forward fuel lines and fitting I.D.’s, to keep fuel velocities between 2, and 4 feet per second.

• Make plumbing runs short and direct.

• Make radius bends in pipe or hose instead of using elbow fittings. Elbows will add the equivalent of seven + feet of fuel

flow restriction to the system. They also generate turbulence.

• Use only, “Full Flow” hose fittings.

• Use hose of adequate length. Don’t connect two or three shorter pieces together.

• Mount pulsation dampers no higher than necessary.

• Size Racor type fuel filters to minimize their pressure drop. It may be necessary to oversize the filter by 150%, or

parallel two smaller filters.

Fixed pressure drops from the fuel tank lift pipe, suction screen, and flow sensors total approximately 5” Hg. This allows 5”
Hg. for hose and pipe plumbing, Racor filter, and pulsation damper. If total inlet vacuum exceeds 10” Hg, the engine may be
difficult to start and fuel starvation may occur at higher Rpm’s.

Approximate Maximum Flow Rates through Schedule 40 Pipe & Fittings for Selected Line Velocity

Pipe/Fitting Size

2 Ft/Sec.

4 Ft/Sec.

10 Ft/Sec.

15 Ft/Sec.

1 / 8” .269” ID

21.6 GPH

43.2 GPH

108 GPH

162 GPH

1 / 4” .364” ID

36.0 GPH

72.0 GPH

180 GPH

270 GPH

3 / 8” .493” ID

72.0 GPH

144 GPH

360 GPH

540 GPH

1 / 2” .622” ID

115 GPH

228 GPH

570 GPH

840 GPH

3 / 4” .824” ID

206 GPH

396 GPH

960 GPH

1,500 GPH

1” 1.049” ID

330 GPH

660 GPH

1,620 GPH

2,460 GPH

1-1 / 4” 1.660” ID

564 GPH

1,140 GPH

2,820 GPH

4,200 GPH

Table 1

Approximate Maximum Flow Rates through Fuel Hose for selected Line Velocity

Fuel Hose Size

2 Ft/Sec.

4Ft/Sec.

10 Ft/Sec.

15 Ft/Sec.

3 / 8 ~ .375” ID

36.0 GPH

72.0 GPH

180 GPH

270 GPH

1 / 2 ~ .500” ID

72.0 GPH

144 GPH

360 GPH

540 GPH

3 / 4 ~ .750” ID

180 GPH

360 GPH

900 GPH

1,500 GPH

1 ~1.000” ID

291 GPH

582 GPH

1,458 GPH

2,190 GPH

Table 2

Approximate Pressure Drop per Foot of Hose & Schd. 40 Pipe @ Selected Flow Rate and Line Velocity

2 Ft/Sec.

4 Ft/Sec.

10 Ft/Sec.

15 Ft/Sec.

Hose size

PSI GPH

PSI GPH

PSI GPH

PSI GPH

3 / 8

<.1 PSI @ 36 GPH

.1 PSI @ 72 GPH

0.6 PSI @ 180 GPH

1.1 PSI @ 270 GPH

1 / 2

<.1 PSI @ 72 GPH

.1 PSI @ 144 GPH

0.5 PSI @ 360 GPH

1.0 PSI @ 540 GPH

3 / 4

<.1 PSI @ 180 GPH

.1 PSI @ 360 GPH

.35 PSI @ 900 GPH

1.0 PSI @ 1,500 GPH

1

<.1 PSI @ 291 GPH

.1 PSI @ 582 GPH

.23 PSI @ 1,458 GPH

0.5 PSI @ 2,190 GPH

Table 3

Approximate Pressure Drop for 2 Full Flow Hose Fittings @ Selected Flow Rate and Line Velocity

2 Ft/Sec.

4 Ft/Sec.

10 Ft/Sec.

15 Ft/Sec.

Fitting-“

PSI GPH

PSI GPH

PSI GPH

PSI GPH

3 / 8

<.1 PSI @ 36 GPH

.10 PSI @ 72 GPH

.55 PSI @ 180 GPH

1.2 PSI @ 270 GPH

1 / 2

<.1 PSI @ 72 GPH

.13 PSI @ 144 GPH

1.0 PSI @ 360 GPH

1.5 PSI @ 540 GPH

3 / 4

<.1 PSI @ 180 GPH

.14 PSI @ 360 GPH

1.3 PSI @ 900 GPH

2.0 PSI @ 1,500 GPH

1

<.1 PSI @ 291 GPH

.10 PSI @ 582 GPH

.45 PSI @ 1458 GPH

1.3 PSI @ 2,190 GPH