beautypg.com

Installation requirements, Correct, Incorrect – Fire Magic Aurora Multi-Housing Built-In Grill A430i-1E1(N,P)-01 User Manual

Page 7

background image

7

INSTALLATION REQUIREMENTS

This grill is designed for outdoor use only. DO NOT use this grill under unprotected fl ammable surfaces.

DO NOT use this grill inside a building, garage, enclosed area, or an unprotected covered area (see

EXHAUST REMOVAL below). DO NOT use this grill in or on a recreational vehicle or boat.

Important:

The grill must have a minimum of 18" (45.7 cm) right, left, and back clearance from unprotected
combustible construction. If installing this grill in a combustible surround, the correct R. H. Peterson
insulating liner must be used.

The control panel MUST remain removable for servicing
(see PARTS LIST).

ENSURING PROPER COMBUSTION AIR AND
COOLING AIRFLOW

Proper airfl ow (Fig. 7-1) MUST be maintained for the
grill to perform as it was designed. If airfl ow is blocked,
overheating and poor combustion will result. Do not
block the 1" (2.5 cm) front air inlet along the bottom of
the control panel or more than 75% of the cooking grid
surface with pans or griddles.

Note: The 1" (2.5 cm)

front air space
a l s o a l l o w s
access to the
drip tray.

EXHAUST REMOVAL

If installed or used under a patio roof, the cooking grid
area must be fully covered by an exhaust hood with a vent.
An exhaust fan with a rating of 1,000 CFM (cubic feet per
minute) (472 liters per second) or more may be necessary
to effectively remove smoke and other cooking by-products
from the area under the hood. Fire Magic Vent Hoods
are available to meet this requirement
. This grill must
not be used under unprotected overhead combustible
construction. THIS UNIT MUST NOT BE LOCATED IN
A FULLY ENCLOSED AREA OF ANY KIND.

GAS-SUPPLY PLUMBING REQUIREMENTS

For natural gas or a household propane system, rigid

1

/

2

"

(1.3 cm) or

3

/

4

" (1.9 cm) black steel pipe or local code-

approved pipe is required to conduct the gas supply to
the unit. Contact your local gas supplier. Connect this
pipe to the required C.S.A.-approved stainless-steel fl ex
connector (attached). An NPT adapter has been provided
for

1

/

2

" pipe. DO NOT use a rubber hose within the grill

enclosure. Apply only joint compounds that are resistant
to all gasses to all male pipe fi ttings except fl are fi ttings.
Make sure to tighten every joint securely.

Note: If

1

/

2

" (1.3 cm) pipe is used with natural gas,

it should be no longer than 20' (6.1 meters).

Important:

An external valve (with a removable
key) in the gas line is necessary for
safety when the grill is not in use. It also
provides for convenient maintenance.

CAUTION: Wind blowing into or across the rear

oven lid vent (Fig. 7-2) can cause
poor performance and/or dangerous
overheating. Orient the grill so that the
prevailing wind blows toward the front of
the grill (Fig. 7-3).

CAUTION: To prevent dangerous overheating, the rear

of the unit must have a minimum clearance
of 4" (10.2 cm) from any backsplash/wall.

GAS SUPPLY AND MANIFOLD PRESSURES:
For natural gas - normal 7" (17.78 cm) water column
(w.c.), minimum 5" (12.7 cm), maximum 10

1

/

2

" (26.7

cm). For propane gas - normal 11" w.c., minimum 10"
(25.4 cm), maximum 13" (33 cm).

REV 0 - 1307081445

L-C2-414

Fig. 7-1

- Ventilation diagram

Left-side

hanger

Fig. 7-4

Flex connector

Left-side

support wall

Orient grill
so prevailing
wind blows
this way.

Fig. 7-3

CORRECT

PLACE GRILL SO PREVAILING

WIND BLOWS TOWARD FRONT

OF GRILL

Equipped wind defl ector will

improve performance of grill.

However, you must still protect

rear oven from prevailing wind.

Rear oven lid vent

INCORRECT

Fig. 7-2

This manual is related to the following products: