The heating foil is manufactured according to the requirements of
the standard EN 60335-2-96 and it must be installed according to
the valid National Standards.
•
The EN 50559 standards requirements must be met. El. installation
must be in accordance with national regulations.
•
The covering of Ecofilm heating foil with 0.1 mm-thick polyester foil 
or 0.2 mm polyethylene foil fulfils the requirements of the EN 60335-
1 standard for class II structures, and the EN 60335-2-96 standard 
for the installation of heating units in the floor or ceiling. 
•
The user must be instructed by the supplier regarding the installa-
tion of floor heating. 
This fact is stated on a label which comes with the product and 
must be glued into the switchboard: this label also informs readers 
that the making of openings is prohibited, as is covering the floor 
with furnishings or fittings without leaving at least a 4 cm gap be-
tween the floor and the bottom surface. 
 
 
 
 
 
 
 
 
 
 
 
 
2. Floor Section – Direct Heating System 
I. FLOATING FLOOR 
 BASE – CONCRETE, CETRIS ETC. 
 
1 - three-layer wooden or laminate floating floor 
2 - floor (limitation) probe in a groove 
3 - PE foil covering, min. 0.2 mm thick 
4 - ECOFILM® floor heating foil 
5 - insulation underlay from extruded polystyrene 
6 - base – concrete, anhydrite, original floor etc. 
II. Under a carpet or PVC 
 
1 - wear layer (PVC, carpet) 
2 - HEAT-PAK 7 mm two-layer glued underlay 
3 - floor (limitation) probe in the groove (embedded) 
4 - PE foil covering, min. 0.2 mm thick 
5 - ECOFILM® fl oor heating foil 
6 - insulation underlay from extruded polystyrene 
7 - base – original floor, concrete anhydrite, etc. 