Fenix ECOFILM SET User Manual
Page 5

5
•
The heating foil is manufactured according to the requirements of
the standard EN 60335-2-96 and it must be installed according to
the valid National Standards.
•
The EN 50559 standards requirements must be met. El. installation
must be in accordance with national regulations.
•
The covering of Ecofilm heating foil with 0.1 mm-thick polyester foil
or 0.2 mm polyethylene foil fulfils the requirements of the EN 60335-
1 standard for class II structures, and the EN 60335-2-96 standard
for the installation of heating units in the floor or ceiling.
•
The user must be instructed by the supplier regarding the installa-
tion of floor heating.
This fact is stated on a label which comes with the product and
must be glued into the switchboard: this label also informs readers
that the making of openings is prohibited, as is covering the floor
with furnishings or fittings without leaving at least a 4 cm gap be-
tween the floor and the bottom surface.
2. Floor Section – Direct Heating System
I. FLOATING FLOOR
BASE – CONCRETE, CETRIS ETC.
1 - three-layer wooden or laminate floating floor
2 - floor (limitation) probe in a groove
3 - PE foil covering, min. 0.2 mm thick
4 - ECOFILM® floor heating foil
5 - insulation underlay from extruded polystyrene
6 - base – concrete, anhydrite, original floor etc.
II. Under a carpet or PVC
1 - wear layer (PVC, carpet)
2 - HEAT-PAK 7 mm two-layer glued underlay
3 - floor (limitation) probe in the groove (embedded)
4 - PE foil covering, min. 0.2 mm thick
5 - ECOFILM® fl oor heating foil
6 - insulation underlay from extruded polystyrene
7 - base – original floor, concrete anhydrite, etc.