Fenix AL-MAT User Manual
Page 8
Regulation
Always use a thermostat with a floor probe for the limitation of the floor temperature for regulation.
The limit temperature of the floor must be set according to the requirements of the producer of the
given floor
covering, with a maximum of 27°C – hygienic limit.
Start-up of heated floors
Concrete, anhydrite and similar bases:
On the first day, set the floor temperature so that it is the same as the room temperature (maximum
18°C).
Increase the floor temperature gradually during
the following days, by 2°C/day up to 27°C.
Maintain the floor temperature at 27°C for a period of three days.
Subsequently, lower the floor temperature by 5°C a day until it reaches the initial temperature.
Afterwards, the floor temperature can be set to the required value and the floor brought into
standard operation.
In other cases, the heating system can be switched on without any start-up procedure.
Warranty, claims
The supplier of ECOFLOOR cable circuits provides a 10-year warranty for
the product’s functionality
starting on the day of installation as confirmed on the certificate of warranty (the installation must be carried
out 6 months from the date of sale, at the latest), providing:
the Certificate of Warranty and documentary evidence of purchase is presented,
the procedure described in this instruction manual is adhered to,
data regarding the composition of the cable in the floor, the connection and the results of measuring
the insulation resistance of the heating cable are provided,
the instruction manual of the manufacturer for the application of sealants is adhered to.