05 troubleshooting guide – Daktronics S SERIES User Manual
Page 10

6
Symptom
Possible Cause
Corrective Action
Main power turned OFF
Green power light is NOT ON
E-Stop button pressed
Key switch turned OFF
Overtravel light is ON
Overtravel light is FLASHING
Over travel limit reached
Over/Under capacity (if load
sensing option is included)
Check over travel limits
Confirm that load is within
the capacity of the hoist
Vortek hoist will not move
when commanded
Main power turned OFF
E-Stop button pressed
Motor overload
Wait for automatic reset
Hoist has reached limit switch
Move hoist in opposite
direction of travel
Circuit breaker tripped on
wireway
Press red reset button at hoist end
(power panel assembly)
Turn key switch ON
Turn main disconnect ON
Release E-Stop button
Turn on Main Disconnect
Check all E-Stop buttons
For service contact:
Daktronics
7200 Rawson Road
Victor, New York 14564
Description and Operation of Indicator Lights
POWER ON: Indicates that Main Disconnect is turned on and the “System Enable” key switch is also
enabled.
OVERTRAVEL FAULT: Indicates that any one of the hoists has traveled too far and is causing a ‘Ground
Out’ condition. In the unlikely event when this light is illuminated, NO hoist will operate. Please call
Daktronics for help on resolving this issue.
OVER SELECT FAULT: Lights up when more than 4 hoists are selected to run at one time and will pre-
vent any hoists from operating. Deselecting hoists will turn this indicator off and enable the hoists to
operate once more.
VOLTAGE/PHASE FAULT: Lights up when voltage is Under or Over by 10% of specified settings. (Set to
specified voltage per installation, either 208v or 480v). This light also lights up when phase reversal is
detected and will prevent the system from operating.
Telephone: 585-924-5000
Fax: 585-924-0545
www.daktronics.com/rigging email [email protected]
Too many hoists selected
Reduce the number of hoists
selected
05
TROUBLESHOOTING GUIDE