Continuation Software Description

Analog Value Object 1

Property

Remark / Value

RW

Object_Identifier

analog-value, instance 1

R

Object_Type

ANALOG_VALUE (2)

R

Object_Name

max. 42 Bytes, default “Watchdog Time”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

Time Constant of Watchdog Timer,
0: Watchdog is inactive, Maximum: 655.34 seconds

RW-E

Status_Flags

IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0

R

Event_State

NORMAL (0)

R

Out_Of_Service

FALSE (0)

R

Units

seconds (73)

R

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

The Watchdog Timer resets Present_Value of all output objects to Relinquish_Default, if BACnet communication fails permanently. The timer is re-
started, when a BACnet message with an APDU is received.
When the timer times out, the priority arrays of all output objects are completely cleared to NULL.