Continuation Software Description
Binary Input Object 1…4
Property
Remark / Value
RW
Object_Identifier
binary-input, instance 1 … 4
R
Object_Type
BINARY_INPUT (3)
R
Object_Name
max. 42 Bytes, default “Input 1” … “Input 4”
RW-E
Description
max. 84 Bytes, default “”
RW-E
Present_Value
INACTIVE (0) / ACTIVE (1),
writable if Out_Of_Service
R
RW
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE:
0 / 1
R
Event_State
NORMAL (0)
R
Out_Of_Service
FALSE (0) / TRUE (1)
RW
Polarity
NORMAL (0) / REVERSE (1)
RW-E
Inactive_Text
max. 20 Bytes, default “Off”
RW-E
Active_Text
max. 20 Bytes, default “On”
RW-E
Notification_Class
Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
1: local broadcast,
2: global broadcast
RW-E
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Function Table for Binary Input
Out_Of_Service
Polarity
Binary Input
Present_Value
OUT_OF_SERVICE
0
0
0
1
0
1
0
0
1
0
1
1
0
0
1
0
0
1
x
1
1
1
0
1
x
1
x: Present_Value is writable and not affected by inputs
Group Object 1…3
Property
Remark / Value
RW
Object_Identifier
group, instance 1 … 3
R
Object_Type
GROUP (11)
R
Object_Name
max. 42 Bytes, default “Group 1” … “Group 3”
RW-E
Description
max. 84 Bytes, default “”
RW-E
Present_Value
Present_Value of Binary Inputs,
see next Table
R
List_Of_Group_Members
see next Table
R
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Members of Groups
Group
Binary Input
1
2
3
4
1
x
x
x
x
2
x
x
3
x
x