4 short form start-up, Hort form start – Bronkhorst Modbus slave interface User Manual
Page 6
BRONKHORST
®
1.4 Short form start-up
All necessary settings for this module are already performed at Bronkhorst.
To follow next steps carefully is the quickest way to get this module operational in your own Modbus environment.
Instruments with combined RS232 / RS485 signal lines and no user interface automatically detect the
bus type at start-up.
Warning: this device uses a vendor specific pin layout on the RJ45 connector that differs from the
Modbus recommended pin layout.
START
Master
present
Set Slave address and
baud rate of instrument
Make sure your Modbus master has been installed to the system
Instruments will be delivered to customers on address 1 and with a baud rate of
19200 baud. The easiest way to change the slave address is by use of the rotary
switches on the instrument. Also you can use the FLOWFIX program to change Slave
address and baud rate via the RS232 connection (it may be needed to restart the
instrument to apply the changes). Slave address and baud rate can also be changed
using the button (if present) on the instrument.
Connect instrument
Physically connect the instrument to the Modbus network.
Test
Test communication between your master and the instrument(s)
Ready
Page 6
Modbus interface
9.17.035