4.4.6 Available parameters

Modbus registers (in the data model) are numbered from 1 to 65536. In a Modbus PDU (Protocol Data Unit) these

registers are addressed from 0 to 65535. This addressing model has been described in section 4.4 of [1].

The following table lists the most commonly used parameters.

MODBUS REGISTERS

PARAMETER NAME PARAMETER

TYPE

ACCESS

PDU ADDRESS

REGISTER NUMBER

REMARK

Hex

Dec

Hex

Dec

Wink

Unsigned char W

0x0000

0

0x0001

1

Value 14592

Initreset

Unsigned char RW

0x000A

10

0x000B

11

Valve output

Unsigned int

RW

0x001F

31

0x0020

32

Range 0..32767

Measure

Unsigned int

R

0x0020

32

0x0021

33

Setpoint

Unsigned int

RW

0x0021

33

0x0022

34

Setpoint slope

Unsigned int

RW

0x0022

34

0x0023

35

Analog input

Unsigned int

R

0x0023

35

0x0024

36

Control mode

Unsigned char RW

0x0024

36

0x0025

37

Sensor type

Unsigned char RW 

0x002E

46

0x002F

47

Capacity unit index

Unsigned char RW 

0x002F

47

0x0030

48

Fluid number

Unsigned char RW

0x0030

48

0x0031

49

Alarm info

Unsigned char R

0x0034

52

0x0035

53

Temperature

Unsigned int

R

0x0427

1063

0x0428

1064

See addr 0xA138

Alarm limit maximum

Unsigned int

RW

0x0C21

3105

0x0C22

3106

Alarm limit minimum

Unsigned int

RW

0x0C22

3106

0x0C23

3107

Alarm mode

Unsigned char RW

0x0C23

3107

0x0C24

3108

Alarm setpoint mode

Unsigned char RW

0x0C25

3109

0x0C26

3110

Alarm new setpoint

Unsigned int

RW

0x0C26

3110

0x0C27

3111

Alarm delay

Unsigned char RW

0x0C27

3111

0x0C28

3112

Reset alarm enable

Unsigned char RW

0x0C29

3113

0x0C2A

3114

Counter value

Unsigned int

RW

0x0D01

3329

0x0D02

3330

See addr 0xE808

Counter unit index

Unsigned char RW

0x0D02

3330

0x0D03

3331

Counter limit

Unsigned int

RW

0x0D03

3331

0x0D04

3332

See addr 0xE818

Counter setpoint mode

Unsigned char RW

0x0D05

3333

0x0D06

3334

Counter new setpoint

Unsigned int

RW

0x0D06

3334

0x0D07

3335

Counter mode

Unsigned char RW

0x0D08

3336

0x0D09

3337

Reset counter enable

Unsigned char RW

0x0D09

3337

0X0D0A

3338

Identification number

Unsigned char RW 

0x0E2C

3628

0x0E2D

3629

Normal step c. resp.

Unsigned char RW 

0x0E45

3653

0x0E46

3654

Stable situation c. resp.

Unsigned char RW 

0x0E51

3665

0x0E52

3666

Open from zero c. resp.

Unsigned char RW 

0x0E52

3666

0x0E53

3667

Calibration mode

Unsigned char RW 

0x0E61

3681

0x0E62

3682

Monitor mode

Unsigned char RW 

0x0E62

3682

0x0E63

3683

Reset

Unsigned char W

0x0E68

3688

0x0E69

3689

Bridge potmeter

Unsigned char RW 

0x0E85

3717

0x0E86

3718

Modbus slave address

Unsigned char RW 

0x0FAA

4010

0x0FAB

4011

Polynomial constant A

Float

RW 

0x8128..0x8129 33064..33065

0x8129..0x812A 33065..33066

Polynomial constant B

Float

RW 

0x8130..0x8131 33072..33073

0x8131..0x8132 33073..33074

Polynomial constant C

Float

RW 

0x8138..0x8139 33080..33081

0x8139..0x81A

33081..33082

Polynomial constant D

Float

RW 

0x8140..0x8141 33088..33089

0x8141..0x8142 33089..33090

Sensor differentiator dn

Float

RW 

0x8158..0x8159 33112..33113

0x8159..0x815A 33113..33114

Sensor differentiator up

Float

RW 

0x8160..0x8161 33120..33121

0x8161..0x8162 33121..33122

Capacity

Float

RW 

0x8168..0x8169 33128..33129

0x8169..0x816A 33129..33130

Fluid name

String (10 bytes) RW 

0x8188..0x818C 33160..33164

0x8189..0x818D 33161..33165

Capacity unit

String (7 bytes) RW 

0x81F8..0x81FB 33272..33275

0x81F9..0x81FC 33273..33276

Fmeasure

Float

R

0xA100..0xA101 41216..41217

0xA101..0xA102 41217..41218

FSetpoint

Float

RW

0xA118..0xA119 41240..41241

0xA119..0xA11A 41241..41242

Temperature

Float

R

0xA138..0xA139 41272..41273

0xA139..0xA13A 41273..41274 See addr 0x0427

Capacity 0%

Float

RW 

0xA1B0..0xA1B1 41392..41393

0xA1B1..0xA1B2 41393..41394

Counter value

Float

RW

0xE808..0xE809 59400..59401

0xE809..0xE80A 59401..59402 See addr 0x0D01

Counter limit

Float

RW

0xE818..0xE819 59416..59417

0xE819..0xE81A 59417..59418 See addr 0x0D03

Counter unit

String (4 bytes) R

0xE838..0xE839 59448..59449

0xE839..0xE83A 59449..59450

Device type

String (6 bytes) R

0xF108..0xF10A 61704..61706

0xF109..0xF10B 61705..61707

BHTModel number

String (14 bytes) RW 

0xF110..0xF116 61712..61718

0xF111..0xF117 61713..61719

Serial number

String (16 bytes) RW 

0xF118..0xF11F 61720..61727

0xF119..0xF120 61721..61728

Customer model

String (16 bytes) RW 

0xF120..0xF127 61728..61735

0xF121..0xF128 61729..61736

Firmware version

String (5 bytes) R

0xF128..0xF12A 61736..61738

0xF129..0xF12B 61737..61739

Page 19