5 TROUBLESHOOTING

5.1 Visual diagnostics

LED indications (if present) can be very useful in case of problems with the instrument.

The green LED is normally used for instrument status indication, like normal operation or special function mode. The

red LED will burn continuously in case of a hardware failure. During normal operation, the red LED is switched on

during frame reception or sending on the Modbus interface.

5.2 Step-by-step

More information can be found in document 9.17.023 Operation instructions digital instruments.

This document can be found at:

http://www.bronkhorst.com/en/downloads/instruction_manuals/

START

Check Slave address and

baud rate

Check all Modbus settings at your master. Master and device settings must be the

same, check baud rate and parity setting.

Check slave address and baud rate of device (slave).

Check cabling and

termination

Check cabling and bus termination of your Modbus system.

Check power supply

Check power supply. Instruments need +15Vdc or +24Vdc.

Ready

Check Master

Reset

Try to reset the instrument and/or restart your master.

Check diagnostics

Check the bus diagnostics string. See below.