Boyertown Regal Oil Furnace Nrg Max User Manual
Page 9

9
Table 7 Direct Drive Blower Specifications
Model HP
Speeds
RPM
Volts
Full
Load
Amp.
Capacitor
370 volt
mfd
Rotation Blower
Model
Blower
Speed
AC
Blower
Speed
Change
Blower
Speed
Heat
REL750
3/4
4
1075
115
9.2
15
CCW
100-10T
Hi
Med
Low
Low
REL1000 3/4 4 1075 115 9.2
15
CCW 100-10T Hi
Med
Hi
Med
Low
REH 750
3/4
4
1075
115
9.2
15
CCW
100-10T
Hi
Med
Hi
Low
REH1000 3/4
4 1075 115 9.2
15
CCW 100-10T Hi
Med
Hi
Med
Low
Table 8 Direct Drive Blower Performance
0.2 In. W.C. Static Pressure
0.5 In. W.C. Static Pressure
High
Med.
High
Med. Low
Low
High
Med.
High
Med. Low
Low
REL-600
1903
1711
1547
1399
1661
1485
1355
1227
REL-750
1903 1711 1547 1399 1661 1485 1355 1227
REL-850
1903
1711
1547
1399
1661
1485
1355
N/R
REL-1000
2466 2150 1839 1600 2072 1859 1610 N/R
REL-1250
2466
2150
1839
N/R
2072
1859
N/R
N/R
REH-600
1745 1550 1376 1250 1480 1343 1175 1043
REH-750
1745
1550
1376
1250
1480
1343
1175
N/R
REH-850
1745 1550 1376 1250 1480 1343 N/R N/R
REH-1000
2283
2130
1901
1717
2007
1832
1644
1501
REH-1250
2283 2130 1901 N/R 2007 1832 N/R N/R
MULTIPLE FURNACES IN COMMON DUCT WORK
Multiple furnaces connected to common duct work, either supply, return, or both supply and return
must be wired so that all furnace blower motors are energized at the same time.
Failure to turn all blowers on at the same time can cause a reversal of air flow in those
units where the blower motor is not operating. This reversal of air flow can cause premature blower,
blower motor, wiring and or heat exchanger failure.
Please consult the factory for specific wiring instructions for your application.
Table 5 Round Duct Equivalent Area
Nominal
Size
4 5 6 7 8 9 10 12
Area in.
2
12.5
19.6
28.3
38.5
50.3
63.6
78.5
113.1
WARNING