beautypg.com

Diagnosis, Diagnosis inputs – BECKHOFF FC7501 User Manual

Page 16

background image

Diagnosis

16

FC750x

5. Diagnosis

Diagnosis Inputs

The FC750x has a variety of diagnostic variables available automatically. They describe the state of the card and
of the Sercos ring:

ActualPhase
The current phase of the Sercos ring is displayed.

RequestedPhase
The phase currently being requested (e.g. by the PLC) is displayed. The card or driver is presently attempting to
activate this phase.

SystemState
Gives more precise information about the current phase:
0xE001 = Phase 0
0xE002 = Phase 1
0xE003 = Phase 2
0xE004 = Phase 3
0xE005 = Phase 4
0xE008 = Break
0xE011 = Phase switch 0 -> 1
0xE012 = Phase switch 1 -> 2
0xE013 = Phase switch 2 -> 3
0xE014 = Phase switch 3 -> 4

SystemError
Indicates the current error state:
0x0000 = No error
0x8005 = Drive addresses are incorrect
0x8006 = HS-timeout (service channel)
0x8007 = Double AT-failure
0x8009 = Optical fibre bus is interrupted
0xD002 = Break
0xD003 = Switch from 2->3 failure (S-0-0127)
0xD004 = Switch from 3->4 failure (S-0-0128)
0xF001 = Configuration error (actual/nominal channel)
0xF002 = Error in the time slot calculation
0xF003 = Incorrect phase setting by the NC
0xF004 = Internal error
0xF005 = Error lifecounter
0xF008 = Double MDT-failure
0xF009 = Double MST-failure
0xF00A = Sync-In signal failure

This manual is related to the following products: