7 analog output channel object – BECKHOFF ILxxxx-B520 User Manual
Page 32

Analog Output Channel Object
29
ILxxxx-B520
7 Analog Output Channel Object
Analog Output Channels
The Analog Output Channel Class allows the access to the IO-Data and
the Register Data of each analog output channel of the ILxxxx-B520 and
the connected extension boxes. At Boot Up the ILxxxx-B520 determines
the number of analog output channels and creates one instance of the
object class for each channel.
The Analog Output Channel Object Class is Vendor specific and within in
the range of the Vendor specific Class Codes.
Class Code:
104 (68hex)
Class Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Description
Semantics of
Value
1
get
Revision
UINT
Revision of implementation
1
2
get
Max. Instance
UINT
Max. number of instances
Instance Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Description
Semantics of Value
1
(01hex)
Get/set Value
Array of
BYTE
Value of analog output
channel
Number of Bytes
differs between ana-
log and special signal
extension boxes
2
(02hex)
get
Value Length
USINT
Value length in Bytes
100
(64hex)
get/set
1
Register 0
DWORD
Value of Register 0 of
the
analog
output
channel
see semantics
:
:
:
:
:
:
106
(6Ahex)
get
Register 6
DWORD
Diagnosis Register
see semantics
:
:
:
:
:
:
163
(A3hex)
get/set
1
Register 63
DWORD
Value of Register 63 of
the
analog
output
channel
see semantics
1: before writing the registers the write protection of the registers has to be disabled.