IL Config Object
23
ILxxxx-B520
IO Error Action
Note
Action to be performed if a fieldbus error occurred.
To activate a new IO error Action setting a device reset has to be per-
formed either by executing a power cycle to the ILxxxx-B520 or by
executing a Reset Service (Service Code 5) to the ILxxxx-B520 Iden-
tity Object (Class Id 1, Instance 1)
Value
Description
0
Leave local IO Cycle
1
Leave local IO Cycle and reset outputs (default)
2
freeze outputs
- Poll produced data type
- COS / Cyclic produced
data type
- Poll / COS / Cylic
consumed data type
Type of IO data produced/consumed via the Poll mode and Change of
State / Cyclic mode
Value
Description
0
Analog and digital IO Data with Status Byte (default)
1
Digital IO Data with Status Byte
2
Analog IO Data with Status Byte
- Bit Strobe produced
data type
Type of IO data produced via the Bit Strobe mode
Value
Description
0
Diagnostic Data (see Attribute extension box diagnosis)
1
Digital Inputs with Status Byte (default)
Device Diagnostics
Note
Enables Diagnostics of complex (analog/special function) extension boxes.
Setting this attribute enables the diagnosis of complex channels which is
needed to read the extension box diagnosis.
To activate the diagnosis functions a device reset has to be per-
formed either by executing a power cycle to the ILxxxx-B520 or exe-
cuting a Reset Service (Service Code 5)to the Identity Object (Class Id
1, Instance 1)
Value
Description
0
Device Diagnostic OFF (default)
1
Device Diagnostic ON