Product Overview
KL5111-0000
7
PROFIBUS Coupler BK3000
In the case of the PROFIBUS coupler BK3000, the Kl5111 is always mapped with 6 bytes of input data
and 6 bytes of output data.
Offset Terminal1= 0
Offset Terminal2 Channel1 = 6
The control/staus byte
must be inserted for
parameterization.
The control/status byte will
be inserted for
parameterization (KL5111).
K-Bus
Profibus bus coupler
BK3000
To the bus terminal
Data H
Data L
C/S
C/S
D1
D0
D2
D4
D3
0
The terminal is
mapped in the
bus coupler.
Interbus Coupler BK4000
By default, the Interbus coupler BK4000 maps the Kl5111 with 6 bytes of input data and 6 bytes of output
data.
Offset Terminal 1= 0
Offset Terminal 2 Channel 1 = 7
The control/status byte
must be inserted for
parameterization.
The control/status byte
will be inserted for
parameterization (KL5111).
K-Bus
Interbus bus coupler
BK4000
To the bus terminal
Nutz H
Nutz L
C/S
C/S
D1
D0
D4
D2
D3
0
The terminal is
mapped in the
bus coupler
Other bus couplers and further information
You will find further information on the mapping configuration of bus couplers in the annex of the
respective bus coupler manual and under the heading of Configuration of Masters.
i
Note
The chapter mapping contains an overview of possible mapping configurations
depending on the parameters that can be set.
Parameterization with the KS2000 Configuration Software
Independently of the field bus system, parameters can be set via the serial configuration interface in the
bus coupler using the Beckhoff KS2000 configuration software.