Technical data, Run -led d+ d- power contacts ci+ ci- +5 v 0 v, Kom -led alarm – BECKHOFF KL5051 User Manual
Page 5

Technical data
KL5051
5
Technical data
Technical data
KL5051
Sensor connection
binary input: D+, D-; binary output: Cl+, Cl-
Power supply
5 V DC via power contacts (KL9505)
Current consumption
typically 85 mA without sensor
Sensor supply
5 V DC
Data transfer rate
1 MHz
Data direction
bidirectional
Signal output
difference signal (RS422)
Signal input
difference signal (RS422)
Electrical isolation
500 V (K-Bus / field voltage)
Current consumption from K-Bus
75 mA typ.
Bit width in the process image
I/O: 2 x 16 bits data, 2 x 8 bits control/status
Weight approx..
80 g
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration/shock resistance
conforms to IEC 68-2-6 / IEC 68-2-27
EMC resistance Burst / ESD
conforms to EN 50082 (ESD, Burst) / EN 50081
Installation position
any
Type of protection
IP20
RUN -LED
D+
D-
Power
Contacts
CI+
CI-
+5 V
0 V
Top View
Contact Assembly
13
D
+ +
Cl
14
D
Cl
5
C
D
6
7
8
1
A
B
2
3
4
KOM -LED
Alarm