BECKHOFF KL3102 User Manual
Page 8
Terminal configuration
8
KL3102
Offset Terminal1 Channel1 = 0
Offset Terminal1 Channel2 = 3
Offset Terminal2 Channel1 = 6
KL 3102 Channel1
KL 3102 Channel 2
The control-/status byte
must be inserted for
parameterization.
K-Bus
Profibus bus coupler
BK3000
To the bus terminal
Data H
Data L
D1 - 0
D0 - 0
D0 - 1
D1 - 1
C/S - 0
C/S
C/S - 1
0
The terminal is
mapped in the
bus coupler.
Interbus Coupler BK4000
By default, the Interbus coupler BK4000 maps the KL3102 with 4 bytes of
input data (2 bytes of user data per channel). Parameterization via the field
bus is not possible. The KS2000 software is required for configuration if
use is to be made of the control /status byte.
Offset Terminal1 Channel1 = 0
Offset Terminal2 Channel1 = 4
Offset Terminal1 Channel2 = 2
Offset Terminal2 Channel1 = 6
The control/status byte
must be inserted for
parameterization (KS2000).
K-Bus
Interbus bus coupler
BK4000
To the bus terminal
D0 - 1
D0 - 0
Data H
Data H
Data H
D1 - 0
D1 - 1
Data L
Data L
0
The terminal is
mapped in the
bus coupler.
Other bus couplers and
further information
You will find further information on the mapping configuration of bus
couplers in the annex of the respective bus coupler manual under the
heading of "Configuration of masters".
i
Note
The annex contains an overview of the possible mapping configurations
depending on the adjustable parameters.
Parameterization with the
KS2000 software
Parameterization operations can be carried out independently of the field
bus system using the Beckhoff KS2000 configuration software via the
serial configuration interface in the bus coupler.