Functional description

6

KL304x and KL305x


Functional description

The analog input terminals
- KL304x process signals in the range between 0 and 20 mA

- KL305x process signals in the range between 4 and 20 mA

with a resolution of 12 bits (4095 increments). They can supply the sensors
from voltage fed in via the power contacts. The power contacts can
optionally be supplied via the standard supply or via a feed terminal with
electrical isolation.

Process data output format In the delivery state the process data are shown in two's complement form

(integer -1 corresponds to 0xFFFF). Other display types can be selected
via the feature register (e.g. sign/amount representation, Siemens output
format).

Measured value

Output

KL304x

KL305x

Decimal

Hexadecimal

0 mA

4 mA

0

0x0000

10 mA

12 mA

16383

0x3FFF

20 mA

20 mA

32767

0x7FFF


LED display

The LEDs indicate the operating state of the associated terminal channels.
Green LED: RUN (not applicable for KL3044 and KL3054)

• On: normal operation

• Off: Watchdog-timer overflow has occurred. If no process data is

transmitted to the bus coupler for 100 ms, the green LEDs go out.

Red LED: ERROR

• On: The limit stop of the A/D converter has been reached. The

current is greater than 21.5 mA.

• Off: normal operation