Register Description

KL304x and KL305x

13


User parameters

R32: Feature register
[0x1106]
The feature register specifies the operating modes of the terminal.

Feature bit

no.

Description of the operating mode

Bit 0

1

User scaling (R33, R34) active [0]

Bit 1

1

Manufacturer scaling (R19, R20) active [1]

Bit 2

1

Watchdog timer active [1]
In the delivery state, the watchdog timer is switched on.

Bit 3

1

Sign / amount representation [0]
Sign / amount representation is active instead of two's-
complement representation. (-1 = 0x8001)

Bit 4

1

Siemens output format [0]
This bit is used for inserting status information on the
lowest 3 bits (see below).

Bit 7 to 5

-

reserved, do not change

Bit 8

1

Over range Protection [1]
If values exceed or fall below the limits of the registers
OVRL (R21) and UNRL (R22), the status bits are set and
the measuring range is restricted accordingly.

Bit 9

1

Limit value 1 active [0]
The process data are compared with limit value 1 (R35),
and appropriate status bits are set.

Bit 10

1

Limit value 2 active [0]
The process data are compared with limit value 1 (R36),
and appropriate status bits are set.

Bit 11

1

Filter 1 active [0], (not possible for KL3044 and KL3054)
filter characteristics see R37

Bit 12

1

Break active [1], do not change

Bit 15 to 13

-

reserved, do not change


If the Siemens output format is selected, the lowest three bits are used for
status evaluation. The process data is represented in bits 3 to 15, with bit
15 representing the sign bit. Scaling of the measurement reading according
to the Siemens standard has to be done via user scaling (R33, R34).

KL3041, KL3042 and KL3044

Bit

Measured value

Bit 15 to 3

Bit 2
X

Bit 1
Error

Bit 0
Overflow

Measured value > 20 mA

0

0

1

Measured value < 20 mA

Process data

0

0

0



KL3051, KL3052 and KL3054

Bit

Measured value

Bit 15 to 3

Bit 2
X

Bit 1
Wire breakage

Bit 0
Overflow/Underflow

Measured value > 20 mA

0

0

1

4 mA

Process data

0

0

0

Measured value < 4 mA

Process data

0

1

1