2 product overview, 1 technical data – BECKHOFF KL1512 User Manual
Page 5

Product Overview
KL1512
3
2 Product Overview
2.1 Technical data
Product name
KL1512
Number of counters
2
Rated load voltage
24 V
DC
(-15% / +20%)
‘0’ signal voltage
-3 V ... 5 V (EN61131-3, Typ 1)
‘1’ signal voltage
15 V ... 30 V(EN61131-3, Typ 1)
Input current
typical 8 mA. (EN61131-3, Typ 1)
Counting frequency
maximum 1 kHz
Counter depth
16 bit
Current consumption from K-Bus
typical 50 mA
Electrical isolation
500 Vrms (K-Bus / field voltage)
Bit width in the process image
2 x 16 bits data, 2 x 8 bits control/status
Configuration
no address settings, configuration via Control and Status Byte
Weight
app. 55 g
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration / Shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
EMC resistance burst / ESD
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
any
Type of protection
IP20