Cyc err wd plc – BECKHOFF BC2000 User Manual
Page 15

Basic Principles
BC2000
14
PLC LED
If the PLC LED lights, the program has started on the BC2000. The LED
flashes while a boot project is being created.
Diagnostic LEDs on the
BC2000
CYC
ERR
WD
PLC
The bus terminal controller interrogates the configuration of the bus
terminals after it has been switched on, then performs exchange of data
with the terminals. This means that the red I/O LED goes out after a fault-
free start-up, and the green I/O LED lights. The green I/O-LED lights with
the PLC timing on the bus terminal controller. If no program is running on
the BC2000, the pre-set cycle time for triggering the terminal bus is used.
CYC
ERR
WD
Meaning
Remedy
lit
off
lit
Telegrams are passing cyclically along
the ring
Inputs are read and outputs are set.
Everything is satisfactory
lit
off
lit
I/O-RUN flashes
The PLC cycle time that has been
set is too long > 100 ms
lit
off
off
The ring is functioning, but the bus
terminal
controller
is
not
being
addressed
Re-examine the control software
or the assignment list
blinking
off
off
The
controller
only
occasionally
accesses the bus. The outputs drop
away.
Re-examine the control software
off
lit
off
(Physical) bus fault, faulty telegrams are
circulating in the ring, e.g. optical fibre
damaged, previous module faulty, plug
not properly inserted
Check:
- whether the optical fibre cable is
inserted
- whether the optical fibre cable is
broken
- whether previous module is
ready for operation
off
blinking
off
Occasional CRC error (green I/O LED
lights)
Inputs are read; outputs are not
updated;
Optical fibre connection damaged
off
off
off
No operating voltage, serious fault, no
function
- Electrical power supply