beautypg.com

BECKHOFF BK7300 User Manual

Page 34

background image

MODBUS

30

BK7300


Coupler Reset (Sub-Function 1)

Sub-function 1 re-initializes the BK7300. Error counters are reset, and the
coupler executes a self-test. No telegrams are either received or sent while
the coupler is being reset.

Sub-function

Data field (query)

Data field (response)

00 01

00 00

00 00

Delete All Counter Contents (Sub-Function 10)

Calling this sub-function deletes the contents of all error counters in the
coupler.

Sub-function

Data field (query)

Data field (response)

00 0B

00 00

Echo Query Data

Bus Communication Error Counter (Sub-Function 11)

Returns the number of faulty communications.

Sub-function

Data field (query)

Data field (response)

00 0C

00 00

CRC error counter

Error Answer Counter (Sub-Function 13)

This counter contains the number of error answer telegrams that the
coupler has sent.

Sub-function

Data field (query)

Data field (response)

00 0D

00 00

Error Answer Counter


Slave Answers (Sub-function 14)

Contains the number of answers that the slave has sent.

Sub-function

Data field (query)

Data field (response)

00 0E

00 00

Slave Massage Count

Unsent Slave Answers (Sub-Function 15)

Contains the number of answers that the slave has not sent. For example,
the slave does not send an answer to a broadcast message.

Sub-function

Data field (query)

Data field (response)

00 0F

00 00

Slave No Response
Count

Number of Error Answers (Sub-Function 16)

Contains the number of error answers that the slave has sent.

Sub-function

Data field (query)

Data field (response)

00 10

00 00

Number of error
answers