Troubleshooting, Fault correction, Troubleshooting 19 – BECKHOFF CP69xx User Manual

Page 20

background image

Troubleshooting

Troubleshooting

Please also refer to chapter

Foreword

.

Pixel errors

Note

Pixel errors in the TFT display are production-caused and represent no
complaint-reason!


Fault correction

Fault Cause Procedure

The Control Panel shows no
function when the Industrial PC has
been started

No power supply to the Industrial
PC

Cable not connected

Check power supply cable


1. Correctly connect cable
2. Call Beckhoff Service

The Industrial PC does not boot
fully

Setup settings are incorrect

Other cause

Check the setup settings

Call Beckhoff Service

Computer boots, software starts,
but control does not operate
correctly

Cause of the fault is either in the
software or in parts of the plant
outside the Control Panel

Call the manufacturer of the
machine or the software

No screen

Transmission rate is too high when
using DVI cables longer than 20 m

Limit transmission rate for
DDC file to 50 kHz

USB error while TwinCAT access
via USB

Cycle time in TwinCAT is set on
10 ms (standard)

Increase the cycle time up to
50 ms till 80 ms

The Control Panel functions only
partially or only part of the time, e.g.
no or dark picture

Defective components in the
Control Panel

Call Beckhoff Service

CP69xx

19