Troubleshooting

6 Troubleshooting

Pixel errors

Note

Pixel errors in the TFT display are production-caused and represent no complaint-
reason!

Anomalies of the Touchscreen

Note

Anomalies of the touchscreen sensor are production-caused and represent no
complaint-reason!



Fault

Cause

Measures

The Control Panel shows no
function

No power supply to the Control
Panel/ Industrial PC

Cable not connected

Check power supply cable

1. Correctly connect cable
2. Call Beckhoff Service

Computer boots, software starts,
but control does not operate
correctly

Cause of the fault is either in the
software or in parts of the plant
outside the Industrial PC

Call the manufacturer of the
machine or the software

No screen

Transmission rate is too high when
using DVI cables longer than 20 m

Limit transmission rate for
DDC file to 50 kHz

Malfunction of the touchscreen

Bad or missing ground connection
of the device

Establish ground connection

Bad or missing ground connection
of the user

User must stand on the floor
with ordinary shoes

USB error while TwinCAT access
via USB

Cycle time in TwinCAT is set on
10 ms (standard)

Increase the cycle time up to
50 ms till 80 ms

The Control Panel functions only
partially or only part of the time, e.g.
no or dark picture

Faulty backlight in the display

Defective components in the
Control Panel

Call Beckhoff Service

Call Beckhoff Service