Usb-e input (x 103), X103 – BECKHOFF CP39xx User Manual
Page 14

Product Description
2.4.3 USB-E Input (X 103)
X103
SG 8-pole M9 built-in-PCB-sold. IP67 BINDER (BINDER 09-0427-30-08 prod. 712 M9X0,5)
View solder connection sided
The Control Panel is connected with the CU8801 USB to USB extended converter box via the USB-
Extended input (X103).
In order to realize a distance of 50 m without hubs, with USB extended the USB signal is converted so
that it can be transferred via 50 m CAT5 cables commonly used for Ethernet wiring. In the Control Panel
the signal is converted back to USB.
Pin
Signal
Pin assignment
1
15 V
15V USB_E
2 GND
GND
3 Tx USB
Rx+
4 RX
USB
Tx+
5 RX
USB
Tx-
6 Tx USB
Rx-
7
15 V
15V USB_E
8 GND
GND
2.4.4 USB interface at the mounting arm adapter (optional)
Optionally the Control Panel is fitted with a USB-2.0 Interface (order option C9900-E274).
The interface is located at the mounting arm adapter behind a screw cap, the protection class accords to
the IP67-standard.
USB Interface
12
CP39xx