Operating Instructions XWA11V

1598003200

Weiss Instruments, Inc. 905 Waverly Ave. Holtsville, NY 11742 631-207-1200 www.weissinstruments.com

7


13. PARAMETER MAP

LABEL

DESCRIPTION

COOLER

VALUES

DEFAULT

**

FREEZER

VALUES

LEVEL

RANGE

ot

Thermostat probe calibration

0

0

Pr2

[-12,0°C <> 12,0°C] [-
21°F <> 21°F]

CF

Temp measurement unit

F

F

Pr2

°C - °F

rES

Resolution (only °C)

in

in

Pr2

dE - in

UT

Display update

60

60

Pr2

0 <> 255 (sec)

OnF

Off function enabling

Y

Y

Pr2

N - Y

ALU

High Temp alarm setting

**

50

30

Pr1

°C[ ALL <> 150,0°]

°F[ ALL <> 302°]

ALL

Low Temp alarm setting

**

25

-20

Pr1

°C[ -50.0° <> ALU]

°F[-58 <> ALU]

AFH

Temp alarm differential

2

2

Pr2

[0,1°C <>25,5°C]

[1°F <> 45°F]

ALd

Temp alarm delay

30

30

Pr1

0 <> 255 (min.)

dAo

Delay of Temp alarm at start-up

1.5

1.5

Pr2

0 <> 24.0 (Hrs / 10 min.)

EdA

Alarm delay at the end of defrost

30

30

Pr2

0 <> 255 (min.)

dot

Delay of Temp alarm after closing
the door

15

15

Pr2

0 <> 255 (min.)

LHt

Light timer

15

15

Pr1

0 <> 255 (min.)

doA

Open door alarm delay

15

15

Pr1

0 <> 255 (min.)

OA1

First relay configuration

Alr

ALr

Pr2

ALr - LHt - OnF

oA2

Second relay configuration

LHt

LHt

Pr2

ALr - LHt - OnF

AOP

Alarm relay polarity

CL

CL

Pr2

OP - CL

i1P

Digital input 1 polarity

op

oP

Pr2

OP - CL

i1L

Door switch to turn light ON

y

y

Pr2

n - Y

i1F

Digital input 1 operating mode

dor

dor

Pr2

EAL - dor- dFr - LHt

i2P

Digital input 2 polarity

CL

cL

Pr2

OP - CL

i2F

Digital input 2 operating mode

Pan

PAn

Pr2

EAL - Pan - dFr - LHt

did

Time interval/delay for digital
input alarm

0

0

Pr2

0 <> 255 (min.)

tbA

Alarm relay disabling

n

n

Pr2

n - Y

PbC

Kind of probe

ntc

ntc

Pr2

PtC - ntC

dP1

Real T° Probe 1

Pr2

(probe value)

rEL

FW release

Pr2

read only

Ptb

Parameter map

Pr2

read only